Fixed Benzene Specific Gas Monitor: Titan

The fixed benzene specific gas detector possesses a dynamic detection range or 0–20 ppm with 0.1 ppm sensitivity to benzene. The Titan can be wall-mounted and it samples gas from the atmosphere once per minute, offering a precise and accurate benzene measurement in under a minute.

This fixed benzene specific gas monitor’s immediate warning alarm system offers two operator configurable levels, safeguarding your workforce ensuring they are safe and well protected according to on-site regulations.

Features

Titan fixed benzene specific gas monitor features continuous, real-time measurement that facilitates the constant monitoring of trends that are communicated via 4-20 mA or RS485. Data is internally stored and is always available for analysis with the remote download feature.

Developed to be easily installed and serviced, the modular design enables installation of the Ex d case well in advance of commissioning. Removal and replacement of the internal service module is possible due to the remotely serviceable plug and play cartridge feature.

Titan - Fixed benzene detector

Video Credit: Ion Science

Ultimate Performance

  • Rapid and accurate detection of benzene down to 0.1 ppm
  • Minute-to-minute sampling offering continuous real-time data
  • Robust separation method delivers benzene specific readings
  • Internally regulated heating for stable operation at extremely high temperatures

Ultimate Safety

  • Clear, easy-to-read display & visual alarms that signal benzene levels
  • Two user-definable independent alarm levels, including optional real-time STEL calculation
  • Two relay outputs deliver immediate warning alarms
  • Compliant with ATEX & IECEx, UL and CSA standards

Ultimate Flexibility

  • Modular design for easy installation and servicing
  • 2-year warranty (when instrument registered online)
  • In-built humidity resistance with no need to compensate
  • Service-free six months operation

Technical Specification

Source: Ion Science

Specification Value
Sensor Type PID, 10.6 eV lamp coupled with selective filtering
Selectivity  Benzene specific within typical petrol chemical matrix
Range 0 – 20 ppm
Measuring Frequency One minute
Lower Limit of Detection 0.1 ppm
Accuracy ±0.1 ppm or ±10%, whichever is greater
Temperature Stability Internally heated
Sample Flow 200 ml/min
Display Graphical BW LCD 64 x 128 pixels with back light
Bright LEDs for normal operation, fault and alarm
Two magnetic switches for menu operation
Approvals II 2G Ex d II B+H2 T4 Gb
Tamb. = -20 °C to +55 °C
IECEx FTZU 140030X
ATEX, EMC
Conforms to UL 61010-1,
UL 60079-0, UL 60079-1
Certified to CAN/CSA-C22.2
Ingress Protection Rating  Designed to IP65 (cable gland dependant)
Humidity 0 – 100% RH
Minimum Service Period 6 months – Hydrophobic & carbon filter replacement
12 months – PID lamp, electrode stack, pump and column replacement
Cable Entry Two 3/4 NPT gland threads
Power Vin (nom) 24 V DC @ 3.2 A (recommended)
Vin (max) 32 V DC @ 2.4 A
Vin (min) 19 V DC @ 4.0 A
Communication Isolated 4 – 20 mA output
Isolated RS 485 Modbus (simplex/half duplex or fully duplex)
USB when lid removed with PC software
Data Storage On board MMC, minimum of 6 months
Relay Output Two isolated outputs, voltage free, 24 V DC @ 1.25 A
Weight and Dimensions 15 kg (33 lb)
219 x 219 x 17 mm (8.6 x 8.6 x 6.8” approx)
Gas Sample Line 10 m max length, PTFE, 6 mm OD, 4 mm ID

All specifications quoted are at calibration point and under the same ambient conditions.
Specifications are based on isobutylene calibration at 20 ˚C, 90% RH and 1000 mBar